Auto recovery circuit breaker
Model:KS-7 |

General |
In addition to the function ( leakage, overload, short, etc.)
of existing ELCB, KS-7 circuit breaker automatically recovers the power line if the breaker is tripped by earth leak, lighting or malfunction, When the causes are cleared. |
Features |
- 2 Type selectable : Auto recovery Mode / Normal mode.
- All-in-one type : auto recovery circuit breaker operated by solenoid and
latch mechanism.
- Surge corresponding of power.
- Easy installation : Both DIN-Rail and screw installation available.
- Overload, Short : Circuit breaker Trip? (No recovering).
- Trip by temporary earth leak, lightning or malfunction -> Automatically
recovers when the cause is cleared.
- Continuous earth leak : The number of auto recoveries during mode, No
recovery.
- Manual off :No recovering (safety guaranteed).
Category |
FUNCTION |
Reset Button |
Button for initializing setting value(10sec,10sec,60sec.) -> auto reset function included |
Test
Button |
Check normal operation by make a current leakage cause.
Auto recovery mode : Trip -> recovery after 10Sec.??? Earth leakage mode : Trip |
Select Mode |
2 Type option |
Auto Recovery |
Auto recovery when Light current leakage and failure happens |
ELCB |
No auto recovery function in previous ELCB. |
|
Specifications |
Items |
Unit |
KS-7 |
Remarks |
Size |
mm |
58 X 95 X 75 |
Proper siwe to replace existing ELCB |
Rated voltage |
V |
220 |
|
Rated current |
A |
30 |
|
Operable temperature |
/span> |
-20 ~ 80 |
|
Rated sensitivity current |
mA |
30 |
|
Rated inoperavle current |
mA |
15 |
|
Automatic reset time |
Sec |
10, 10, 60 |
Adjustable |
Short circuit |
Sec |
< 0.03 |
|
Short-circuited current |
kA |
2.5 |
|
Installation method |
|
Screw / DIN-Rail |
|
Remarks |
|
Dead operation type on shock
wave.
Protection type from Over load
and short circuit |
Cable/Wireless Communication module
(optionable) |
|
Standard |
- Korean standards association. KS C 4613
- EK Listed (Safety certification of electrical appliances. K 60947-2)
- CB Listed (certification Body) (IEC 60947-2)
- KERI Test reports - EMC(EMI+EMS)
- K Listed (Korea)
- CE Listed
- TUV GS Listed |
|
|